Catalog 1308242
Issued 3-03 (PDF Rev. 6/07)
KILOVAC
WD series
DIN Rail or Screw Mounted
Protective Relays
•
•
•
•
•
•
WD25 Paralleling (Synch Check) Relays
WD2759 Over/undervoltage Relays
WD32 Reverse Power Relays
WD47 Phase Sequence Relays
WD5051 Single- or Three-Phase Overcurrent Relays
WD81OU Over/Underfrequency Relays
File E58048
DIN EN50022-35
Users should thoroughly review the technical data before selecting a product
part number. It is recommended that user also seek out the pertinent approvals
files of the agencies/laboratories and review them to ensure the product meets
the requirements for a given application.
Overview
Outline Dimensions
The WD series offers several different models of protective relays in a
common package that is suitable for either DIN rail or screw mounting.
These flexible, multifunction devices offer user selectable voltages, sense
currents and frequencies. Adjustable time delays are standard. This allows
a single part number to be suitable for multiple applications, thereby reducing inventory costs.
16 X M3.5
1.38
(35.0)
2.87
(73.0)
Specifications common to all models
Power Consumption: 2.5VA, maximum.
Contact Ratings: 5 amps, resistive, at 120VAC.
5 amps, resistive, at 30VDC.
Isolation from Control to Sense Inputs: 2,500VAC.
Mechanical Life: 10 million operations.
Shock: 10g.
Vibration: 0.062 (1.57) double amplitude at 10-55 Hz.
Terminals: M3.5 screws.
Maximum Wire Size: 2 x 24 AWG (2.5mm2) solid to DIN 46288 or 2 x 16
AWG (1.5mm2) stranded w/end sleeves.
Operating Temperature Range: -40°C to +60°C.
Storage Temperature Range: -55°C to +85°C.
Operating Humidity (Max.): 90%, non-condensing.
Enclosure: Plastic case (not sealed).
Mounting Options: Snap mounts on standard DIN rail (DIN-EN 50022-35)
or panel mounts with M4, M5, #8 or #10 screws.
Weight: 14.4 oz. (400g) approximately.
4.41
(112.0)
0.35
(9.0)
2.95
(75.0)
Installation and Maintenance Information
Installation: To mount the WD series protective relay on a DIN rail, hook
the top edge of the cutout on the base of the case over one edge of the
DIN rail, then press the opposite side of the cutout containing the release
clip over the opposite side of the DIN rail. To remove or reposition the relay, lever the release clip and move the relay as required. WD series relays
should be installed in a dry location where the ambient temperature will be
within the operating temperature range.
Maintenance: WD series protective relays are solid state devices that
require no maintenance. They are not designed to be serviced by the user.
Consult KILOVAC customer service at 805-220-2023 if repairs should be
necessary.
Dimensions are shown for refer-
1308 ence purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
M5
M4
2.36
(60.0)
2.36
(60.0)
1.97
(50.0)
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.